Load flow analysis of Industrial plant
| Author(s) | : | Ashokkumar Parmar |
| Institution | : | Electrical Engineering Department, Shantilal shah Engineering College, Bhavnagar |
| Published In | : | Vol. 5, Issue 3 โ March 2018 |
| Page No. | : | 7-15 |
| Domain | : | Engineering |
| Type | : | Research Paper |
| ISSN (Online) | : | 2348-4470 |
| ISSN (Print) | : | 2348-6406 |
The Power-system analysis is mainly performed to predict or enhance the performance of an existing systemsor system is being plan. Design of the industrial power system is slightly different from radial power systems. It isperformed to fulfill different objectives of industrial plant namely safety, reliable service, high-power quality, and lowcapital and operating costs. To plan the industrial power system, different kind of power system analysis are requiredsuch as low flow analysis, short circuit analysis, relay coordination, motor starting analysis, power factor corrections,stability analysis etc. In this paper, the load flow analysis of 6.6 kV industrial plants is presented using ElectricalTransient Analysis Program -7.5.5(ETAP). Load flow is conducted using NR Method. The plant is supplied from the inplant generation (2*16.5 MW Existing and 11.8 MW-newly installed). The external grid supply is used for black start ofTGโs.17.5 MW of existing load become 24 MW after expansion. So this study is done for check feasibility of load andgeneration surplus and operating philosophy selection.
Ashokkumar Parmar, “Load flow analysis of Industrial plant”, International Journal of Advance Engineering and Research Development (IJAERD), Vol. 5, Issue 3, pp. 7-15, March 2018.